Is there any twisted pair available to the gate?
That would help to reduce interference.

----- Original Message ----- 
From: <[EMAIL PROTECTED]>
To: "Charles Patterson" <[EMAIL PROTECTED]>
Cc: <kxt@kxthelp.com>
Sent: Monday, April 11, 2005 10:00 PM
Subject: Re: KX-T: KX-TA624 Gate Problem - Come on "Old Timers!"


>
> Thanks for the good ideas!  The distance is about 450feet with 18/6, good
> quality, brand new in pvc conduit but not twisted (we did not install,
> gate company did it). We did have a surge supp. on it but removed it today
> to no avail.
>
> Do not have the DTMF tester but I can try a different port in case it just
> doesnt like #5 that it is currently in.  Thanks for the input, Nick
>
>
>> Here is what comes to mind:
>>
>> weak tones?
>>     what's the distance to gate (as Harry said)
>>     quality of line (quad wire or twisted pair?), is it old?
>>     does the line run through surge protectors or other "stuff"?
>>
>> Do you have a DTMF decoder?  That could see if the tones are being
>> produced
>> ok. Some units will also show the signal level (compare gate end with the
>> ksu end).
>>
>> Also, monitor the line to see if the tones sound ok all the time, could 
>> be
>> noise on the line?
>>
>> Try a
>
> different port on the KSU?  (does it work through CO port or EXT
>> port?)
>>
>> most of all, have fun!
>> Charles
>>
>> ----- Original Message -----
>> From: <[EMAIL PROTECTED]>
>> To: <kxt@kxthelp.com>
>> Sent: Monday, April 11, 2005 3:27 PM
>> Subject: KX-T: KX-TA624 Gate Problem - Come on "Old Timers!"
>>
>>
>>> Please Help.  My customer has a Linear RE1 gate controller which I have
>>> connected directly into a port on the 624 and it works just fine as far
>>> as
>>> visitors calling in and ringing and then opening the gate remotely.
>>> Typical gate controller that works on DTMF tones, nothing special.
>>>
>>> What is driving us nuts is when the client wants to "call" out to the
>>> gate, open it and then lock it open.  About 70% of the time the gate
>>> unit
>>> acts as if it is not hearing the tones properly from the 624. The gate
>>> requires "##81#" to open and "##83#" to close.  Many times the RE1
>>> digital
>>> attendent will say "invalid code" after the first "#" or the gate unit
>>> will just "lock up" during the process as if alot of buttons were
>>> pressed
>>> on the phone.  I know this really sounds like a gate operator problem
>>> but
>>> it is not, the Linear unit has been completely replaced and we think we
>>> may be starting to see a pattern where it is occuring on 2 particular
>>> phones only but this is still up in the air.
>>>
>>> Maybe a problem with using the # sign? Noise? Some stange
>>> incompatibility?
>>> DTMF tones off pitch? To long? To short?
>>>
>>> The real difficult part is that it works fine sometimes or possibly from
>>> certain phones. Whew! never seen this in 20+ years.
>>>
>>> Thanks, Nick   Astech Security / Strategic Home Media
>>>
>>>
>>> _________________________________________________________________
>>> KX-T Mailing list --- http://kxthelp.com/
>>> Subscription changes: http://kxthelp.com/mailman/listinfo/kxt
>>>
>>>
>>
>>
>>
>>
>
>
>
> _________________________________________________________________
> KX-T Mailing list --- http://kxthelp.com/
> Subscription changes: http://kxthelp.com/mailman/listinfo/kxt
>
> 




_________________________________________________________________
KX-T Mailing list --- http://kxthelp.com/
Subscription changes: http://kxthelp.com/mailman/listinfo/kxt

Reply via email to