Bill,
That is a great point. As it stands, the box
ahead of the residence does contain a main
breaker. If we get rid of that breaker and turn
it into a lugs only panel, it would satisfy the
requirements. I wonder how that would pan out,
since the wiring runs through this other building.
Thanks,
Drake
At 12:49 PM 7/31/2008, you wrote:
Content-Type: multipart/alternative;
boundary="----=_NextPart_000_006F_01C8F303.83492700"
Content-Language: en-us
Drake,
690.64 relates everything to the service
disconnects. All the rest of this is semantics.
As long as the PV connection is upstream of the
service disconnect (i.e. in between the service
disconnect and the service meter), it is
considered a line side service connection.
If there is no way to turn off the residential
service in the panel with the feed-thru lugs,
there is no service disconnect for the
residential service yet. That way if the
connection were on the line side of the first
service disconnect for the residence (one of two
services at the site, both coming from the same
service dropto get all the semantics proper),
it is considered a line-side connection. So what is it
.?
Bill.
From: [EMAIL PROTECTED]
[mailto:[EMAIL PROTECTED]
On Behalf Of Drake Chamberlin
Sent: Thursday, July 31, 2008 9:13 AM
To: RE-wrenches
Subject: Re: [RE-wrenches] Gray code area
At 03:24 PM 7/30/2008, you wrote:
According to the two paragraphs above, the
commercial building has two commercial
services??? One will receive PV and one will not??
One service is for the commercial building and
one is for the residence. There is one service
drop to two meters. Both services will be fed PV.
Drake Chamberlin
Athens Electric
OH License 44810
CO License 3773
740-448-7328
303-328-5533
_______________________________________________
List sponsored by Home Power magazine
RE-wrenches@lists.re-wrenches.org
http://lists.re-wrenches.org/listinfo.cgi/re-wrenches-re-wrenches.org
List rules & etiquette:
http://www.re-wrenches.org/etiquette.htm
Check out participant bios: www.mrsharkey.com/wrenches/
Drake Chamberlin
Athens Electric
OH License 44810
CO License 3773
740-448-7328
303-328-5533
_______________________________________________
List sponsored by Home Power magazine
RE-wrenches@lists.re-wrenches.org
http://lists.re-wrenches.org/listinfo.cgi/re-wrenches-re-wrenches.org
List rules & etiquette:
http://www.re-wrenches.org/etiquette.htm
Check out participant bios: www.mrsharkey.com/wrenches/