Peter, I’d recommend 2-0 copper for this. Overkill? Perhaps, but the battery cables are probably the cheapest vital part of the system. Anything you can do to make life a bit better for the batteries will pay off. A few extra bucks for cable is a lot cheaper than one warrantee site visit.
Cobra “x-flex” cable is MTW THW fine strand, NEC compliant, and easy to bend in small spaces. Hilton Hilton Dier III Renewable Energy Design Missisquoi River Hydro LLC _______________________________________________ List sponsored by Redwood Alliance List Address: RE-wrenches@lists.re-wrenches.org Change listserver email address & settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org List rules & etiquette: www.re-wrenches.org/etiquette.htm Check out or update participant bios: www.members.re-wrenches.org