Re: [RE-wrenches] Generac Warranty claim ECOGEN 15k (Dana)

2019-07-28 Thread Gary Willett
Maverick: I have a 15kW EcoGen. Please send the oil line correction. Thanks! Gary > On Jul 27, 2019, at 10:57 PM, Maverick Brown > wrote: > > Mine died from brushes , I guess catching fire, and that was precipitated by > an oil leak on the upper oil hose. The crimp-on fitting was allowing oil

Re: [RE-wrenches] Generac Warranty claim ECOGEN 15k (Dana)

2019-07-27 Thread David Palumbo
Sent: Saturday, July 27, 2019 10:57 PM To: RE-wrenches Subject: Re: [RE-wrenches] Generac Warranty claim ECOGEN 15k (Dana) Mine died from brushes , I guess catching fire, and that was precipitated by an oil leak on the upper oil hose. The crimp-on fitting was allowing oil to bypass the clamp

Re: [RE-wrenches] Generac Warranty claim ECOGEN 15k (Dana)

2019-07-27 Thread Maverick Brown
Mine died from brushes , I guess catching fire, and that was precipitated by an oil leak on the upper oil hose. The crimp-on fitting was allowing oil to bypass the clamp, spray on the engine and generator head. There is vent hole right on the top of generator head in a perfect place below the oi

Re: [RE-wrenches] Generac Warranty claim ECOGEN 15k (Dana)

2019-07-27 Thread Chris Mason
When you say it died, what was the problem? On Sat, Jul 27, 2019 at 5:43 PM Jason Jackson < ja...@hakaienergysolutions.com> wrote: > Same experience here in Canada. We installed two Ecogens last year, > against our better judgement. Both were dead in under 12 months. One was > rebuilt under warr

Re: [RE-wrenches] Generac Warranty claim ECOGEN 15k (Dana)

2019-07-27 Thread Jason Jackson
Same experience here in Canada. We installed two Ecogens last year, against our better judgement. Both were dead in under 12 months. One was rebuilt under warranty and promptly died again, no coverage in that case. Another was refused warranty as it has been used (sparingly) as prime power during