call IBM hardware support.\
In the mean time use REMOVE=NO and the go into the robot and remove the
tape by hand. When you close the door the robot will do a 'minor'
inventory update and will now show the slot as empty.
.. joe.f.
Joseph A Faracchio, Systems Programmer, UC Berkeley
On Wed, 1
t: Re: Very Strange Problem related to IBM 3494 library
Author: rbs ([EMAIL PROTECTED]) at internet
Date:15-02-01 1:25 AM
> 3.) I get following message on the library manager console:
>
> A cartridge could not be released from Gripper 1 , Accessor A
Grippage problems c
> 3.) I get following message on the library manager console:
>
> A cartridge could not be released from Gripper 1 , Accessor A
Grippage problems can indicate an alignment problem in the 3494 frame.
The 3494's robot has no "eyes" to see where it's going, but rather
remembers where all pos
We experience the same problem. The solution was to use cardboard to shield
the light.
-Original Message-
From: Davidson, Becky [mailto:[EMAIL PROTECTED]]
Sent: Wednesday, February 14, 2001 2:14 PM
To: [EMAIL PROTECTED]
Subject: Re: Very Strange Problem related to IBM 3494 library
As
That's what my CE thought for a while too. Removing the flourescent from
above the 3494 gave temporary relief, but the real problem was that the
door was ajar just enough to make the upper portion of the row opposite the
hinge occasionally unavailable. Once he levelled off the door, no more
prob
As strange as it sounds we have had problems with our library with the
ambient light. Cover the window above that section and see if it fixes the
problem.
Hope that helps.
-Original Message-
From: Mahesh Babbar [mailto:[EMAIL PROTECTED]]
Sent: Wednesday, February 14, 2001 6:32 AM
To: [E