I'm glad you found that bug.   I saw that problem last year during an 
installation, but thought it was due to the controller it was linked to.

I ended up not using the first bit a few times.

Good catch!

Thanks,

Dave

On 3/27/2011 11:44 AM, Les Newell wrote:
> ClassicLadder had a bug in it's Modbus implementation if you read more
> than 8 inputs or coils. The first input bit is not read correctly and
> ends up with strange values.
> I don't know the correct way to submit a fix using Git but the fix is
> simple. In protocol_modbus_master.c, a break; needs to be inserted  in
> line 321. Currently it falls through to the next case.
>
> Les
>
> ------------------------------------------------------------------------------