Gábor Szabados schrieb am Freitag, 17. Mai 2024 um 14:46:55 UTC+2:

As I remember the EU specs is 50Hz +/-1%, so all those look good to me.


No. The tolerance is much smaller. +-0.02 Hz (0.04%) is the normal 
operation range. Up to +-0.2 Hz (0.4%) the European electicity 
administration uses standardized and automated processes to stabilize the 
frequency. Outside that range the situation is considered dangerous. Real 
people get involved. Below 49 Hz they start switching off load. Above 50.2 
Hz private photovolatics inverters start reducing power output.
 

-- 
You received this message because you are subscribed to the Google Groups 
"weewx-user" group.
To unsubscribe from this group and stop receiving emails from it, send an email 
to weewx-user+unsubscr...@googlegroups.com.
To view this discussion on the web visit 
https://groups.google.com/d/msgid/weewx-user/56185fef-3051-4370-9d19-7b2afabe5ac1n%40googlegroups.com.