If the inside of a 3R enclosure isn't considered dry enough for a buchanan
crimp/cap, then there's millions of 3R panels with breakers and busbars in
them that would have the same problem.
Brian Mehalic
NABCEP Certified Solar PV Installation Professional™ R031508-59
National Electrical Code® CMP-4
Adam,
I assume it’s a NYSERDA inspector that’s pushing back, correct? We’ve dealt
with this issue a number of times, and while I will argue until I’m blue in the
face that the code does not consider the inside of a properly installed NEMA 3R
enclosure a damp/wet location, NYSERDA has not accept