Re: [RE-wrenches] Cable Tray Marking

2020-09-02 Thread Ray
This is interesting, because we were considering cable trays, too.  My guess is that both requirements would apply.  Picky, but I don't see that 690 exempts the requirements of 392. One is for PV, one is for over 600 v.  Some code iteration in the future might have combined language for PV over

[RE-wrenches] Cable Tray Marking

2020-09-02 Thread Corey Shalanski