I have been informed [long ago] that not equally weighting a generators output
can cause excessive & uneven wear on the windings of a generator.
Way Back in the day, folks [old wrenches] used to place an additional load [hot
water element, heat lamps...] on the unused leg to balance out a 240 vac
Hi All,
My question is can a single Magnum remote run 2 inverters each as master for
120v?
I’ve got a client with a 3 phase generator, and I need two phases, but I don’t
need 240v.
1. I can’t change the generator
2. Two phases because I can’t load one phase that heavily.
I can do 2 Outback