I have heard AC DC no difference. However, I have experienced failure of these connectors via insulation softening in J boxes on the roof. The plastic is not thermal set and it will distort if pressured against the side of the box. This has never been a problem for interior wiring only in the solar case outside.
On Fri, Jun 1, 2018 at 4:50 PM, James Rudolph <jamesrudolp...@gmail.com> wrote: > Aloha Wrenches, > Does anyone know if Ilsco Insulated Tap Connectors at DC rated? > I looked on their cut sheet, and even called the Cincinnati and I was not > able to confirm this? > > Does anybody know this, or have a better connector to use? > > Mahalo in advance, > > *James B. Rudolph* > > *Hawaii Unifed* > > *Director of Energy* > > *ES Electrician # 10816* > > *NABCEP Certified PV Installer # 091209-155* > > *808.594.9969* > > > > > > > _______________________________________________ > List sponsored by Redwood Alliance > > List Address: RE-wrenches@lists.re-wrenches.org > > Change listserver email address & settings: > http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org > > List-Archive: http://www.mail-archive.com/re-wrenches@lists.re-wrenches. > org/maillist.html > > List rules & etiquette: > www.re-wrenches.org/etiquette.htm > > Check out or update participant bios: > www.members.re-wrenches.org > > >
_______________________________________________ List sponsored by Redwood Alliance List Address: RE-wrenches@lists.re-wrenches.org Change listserver email address & settings: http://lists.re-wrenches.org/options.cgi/re-wrenches-re-wrenches.org List-Archive: http://www.mail-archive.com/re-wrenches@lists.re-wrenches.org/maillist.html List rules & etiquette: www.re-wrenches.org/etiquette.htm Check out or update participant bios: www.members.re-wrenches.org