Hey Wrenches & Nick Soleil (with whom I worked at APS for a time I believe...),
I'm not familiar with Enphase commercial applications and am currently working
through a commercial design. Enphase, on their M215 datasheets claim up to 25
micros per branch, at 1.0A each, with each branch terminating at a 20A breaker.
By my calculations, 25 micros at 1.0A each (25A*1.25=31.25A) need to terminate
at a 40A breaker. Anyone know what I'm missing or know how the 20A breaker
design gets past the AHJ?
Eric Stikes
SunHarvest