According to the MIB in the snmp_exporter generator folder, 4.5.1. It's also worth noting, this isn't just upsHighPrecBatteryPackCartridgeReplaceDate, it's 106 others as well. I was cautious posting the whole thing here at once cause I didn't want to post a wall of text as my first post. Here's the pastebin https://pastebin.com/9trFyUG6
Here's the pastebin for the entire generated snmp.yml https://pastebin.com/grCs0Kgx Here's the manual walk: root@server:# snmpwalk -v1 -c public <IP> 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8 SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.1.1.1 = STRING: "11/05/2025" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.1.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.2.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.2.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.3.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.3.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.4.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.4.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.5.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.5.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.6.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.6.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.7.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.7.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.8.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.8.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.9.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.9.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.10.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.10.1.2 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.11.1.1 = STRING: "01/01/2000" SNMPv2-SMI::enterprises.318.1.1.1.2.3.10.2.1.8.11.1.2 = STRING: "01/01/2000" thanks for the help so far. On Wednesday, November 22, 2023 at 5:15:34 PM UTC-5 Ben Kochie wrote: > Can you find upsHighPrecBatteryPackCartridgeReplaceDate in your snmp.yml? > What version of PowerNet-MIB do you have? > > This is what I get when I generate your config: > - name: upsHighPrecBatteryPackCartridgeReplaceDate > oid: 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8 > type: DisplayString > help: The battery cartridge estimated battery replace date. - > 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8 > indexes: > - labelname: upsHighPrecBatteryPackIndex > type: gauge > - labelname: upsHighPrecBatteryCartridgeIndex > type: gauge > > Can you provide a manual snmpwalk output of that OID > (1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8`)? > > Since you're not dropping the source index on this, that should not > produce duplicates. > > On Wed, Nov 22, 2023 at 11:06 PM Neil Stottler <[email protected]> wrote: > >> Hello! I am trying to scrap multiple APC UPS's on my network via snmpv1, >> one works great, one does not work at all with this error. >> 107 error(s) occurred: * collected metric >> "upsHighPrecBatteryPackCartridgeReplaceDate" { >> label:{name:"upsHighPrecBatteryCartridgeIndex" value:"1"} >> label:{name:"upsHighPrecBatteryPackCartridgeReplaceDate" >> value:"01/01/2000"} label:{name:"upsHighPrecBatteryPackIndex" value:"9"} >> gauge:{value:1}} was collected before with the same name and label values >> >> here is my generator.yml config >> --- >> auths: >> public_v1: >> version: 1 >> public_v2: >> version: 2 >> >> modules: >> # Default IF-MIB interfaces table with ifIndex. >> if_mib: >> walk: [sysUpTime, interfaces, ifXTable] >> lookups: >> - source_indexes: [ifIndex] >> lookup: ifAlias >> - source_indexes: [ifIndex] >> # Uis OID to avoid conflict with PaloAlto PAN-COMMON-MIB. >> lookup: 1.3.6.1.2.1.2.2.1.2 # ifDescr >> - source_indexes: [ifIndex] >> # Use OID to avoid conflict with Netscaler NS-ROOT-MIB. >> lookup: 1.3.6.1.2.1.31.1.1.1.1 # ifName >> overrides: >> ifAlias: >> ignore: true # Lookup metric >> ifDescr: >> ignore: true # Lookup metric >> ifName: >> ignore: true # Lookup metric >> ifType: >> type: EnumAsInfo >> # Default IP-MIB with ipv4InterfaceTable for example. >> ip_mib: >> walk: [ipv4InterfaceTable] >> >> #snmpv2 mib >> #hostresoruces mib >> >> # APC/Schneider UPS Network Management Cards >> # >> # Note: older management cards only support SNMP v1 (AP9606 and >> # AP9607, possibly others). Older versions of the firmware may only >> # support v1 as well. If you only have newer cards you can switch to >> # version v2c or v3. >> # >> # The management cards have relatively slow processors so don't poll >> # very often and give a generous timeout to prevent spurious >> # errors. Alternatively you can eliminate the interface polling (OIDs >> # beginning with 1.3.6.1.2.1) to reduce the time taken for polling. >> # >> # MIB: >> https://download.schneider-electric.com/files?p_File_Name=powernet426.mib >> # Guide: http://www.apc.com/salestools/ASTE-6Z5QEY/ASTE-6Z5QEY_R0_EN.pdf >> # Download site: http://www.apc.com/us/en/tools/download/index.cfm >> apcups: >> walk: >> - 1.3.6.1.4.1.318.1.1.1.2 # upsBattery >> - 1.3.6.1.4.1.318.1.1.1.3 # upsInput >> - 1.3.6.1.4.1.318.1.1.1.4 # upsOutput >> - 1.3.6.1.4.1.318.1.1.1.7.2 # upsAdvTest >> - 1.3.6.1.4.1.318.1.1.1.8.1 # upsCommStatus >> - 1.3.6.1.4.1.318.1.1.1.12 # upsOutletGroups >> - 1.3.6.1.4.1.318.1.1.10.2.3.2 # iemStatusProbesTable >> - 1.3.6.1.4.1.318.1.1.26.4.3 # rPDU2DeviceStatusTable >> - 1.3.6.1.4.1.318.1.1.26.6.3 # rPDU2PhaseStatusTable >> - 1.3.6.1.4.1.318.1.1.26.8.3 # rPDU2BankStatusTable >> - 1.3.6.1.4.1.318.1.1.26.10.2.2 # >> rPDU2SensorTempHumidityStatusTable >> lookups: >> - source_indexes: [upsOutletGroupStatusIndex] >> lookup: upsOutletGroupStatusName >> drop_source_indexes: true >> - source_indexes: [iemStatusProbeIndex] >> lookup: iemStatusProbeName >> drop_source_indexes: true >> overrides: >> rPDU2BankStatusLoadState: >> type: EnumAsStateSet >> upsAdvBatteryCondition: >> type: EnumAsStateSet >> upsAdvBatteryChargingCurrentRestricted: >> type: EnumAsStateSet >> upsAdvBatteryChargerStatus: >> type: EnumAsStateSet >> >> my snmp.yml is rather long so I can post that later on if someone has an >> idea. >> >> -- >> You received this message because you are subscribed to the Google Groups >> "Prometheus Users" group. >> To unsubscribe from this group and stop receiving emails from it, send an >> email to [email protected]. >> To view this discussion on the web visit >> https://groups.google.com/d/msgid/prometheus-users/1cd90fac-c4c2-413b-9509-278385346f51n%40googlegroups.com >> >> <https://groups.google.com/d/msgid/prometheus-users/1cd90fac-c4c2-413b-9509-278385346f51n%40googlegroups.com?utm_medium=email&utm_source=footer> >> . >> > -- You received this message because you are subscribed to the Google Groups "Prometheus Users" group. To unsubscribe from this group and stop receiving emails from it, send an email to [email protected]. To view this discussion on the web visit https://groups.google.com/d/msgid/prometheus-users/c4c0a9b7-bc88-4495-b409-e4ef5710a067n%40googlegroups.com.