I use APC PowerNet MIB 4.2.6. My generator.yaml:
modules:
template_acrd_602:
version: 3
max_repetitions: 25
retries: 3
timeout: 30s
walk:
- coolingUnitStatusAnalogTableIndex
- coolingUnitStatusAnalogDescription
- coolingUnitStatusAnalogValue
I try:
# curl -sw ''
'http://127.0.0.1:9116/snmp?module=template_acrd_602&target=hostname'
And receive (the original output contains dozens of metrics, I shrank it):
coolingUnitStatusAnalogDescription{coolingUnitStatusAnalogDescription="Air
Filter Run Hrs",coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex
="1"} 1
coolingUnitStatusAnalogTableIndex{coolingUnitStatusAnalogTableIndex="44",
coolingUnitTableIndex="1"} 44
coolingUnitStatusAnalogValue{coolingUnitStatusAnalogTableIndex="44",
coolingUnitTableIndex="1"} 4472
And it's ok. But if I add a lookup section into generator.yaml like this:
modules:
template_acrd_602:
version: 3
max_repetitions: 25
retries: 3
timeout: 30s
walk:
- coolingUnitStatusAnalogTableIndex
- coolingUnitStatusAnalogDescription
- coolingUnitStatusAnalogValue
lookups:
- source_indexes: [coolingUnitStatusAnalogTableIndex]
lookup: coolingUnitStatusAnalogDescription
I expect to receive an output something like this:
coolingUnitStatusAnalogDescription{coolingUnitStatusAnalogDescription="Air
Filter Run Hrs",coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex
="1"} 1
coolingUnitStatusAnalogTableIndex{coolingUnitStatusAnalogDescription="Air
Filter Run Hrs"coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex=
"1"} 44
coolingUnitStatusAnalogValue{coolingUnitStatusAnalogDescription="Air Filter
Run Hrs"coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"}
4472
But actually I receive:
coolingUnitStatusAnalogDescription{coolingUnitStatusAnalogDescription="",
coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"} 1
coolingUnitStatusAnalogTableIndex{coolingUnitStatusAnalogDescription="",
coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"} 44
coolingUnitStatusAnalogValue{coolingUnitStatusAnalogDescription="",
coolingUnitStatusAnalogTableIndex="44",coolingUnitTableIndex="1"} 4472
What am I doing wrong? Help please. Thank you!
OID description you could get on web site
<https://cric.grenoble.cnrs.fr/Administrateurs/Outils/MIBS/?oid=coolingUnitStatusAnalogTableIndex>
--
You received this message because you are subscribed to the Google Groups
"Prometheus Users" group.
To unsubscribe from this group and stop receiving emails from it, send an email
to [email protected].
To view this discussion on the web visit
https://groups.google.com/d/msgid/prometheus-users/489060ca-6376-4f51-8d91-f7af8b72af2do%40googlegroups.com.